Dry Riser testing to NFPA standards

Dry Riser testing to NFPA standards

The testing team were at USAF Lakenheath today carrying out a 200PSI, (13.8 Bar), two hour soak test to the NFPA standards as requested by the client. With the system being around thirty years old, the original valves failed at 6 Bar which was no real surprise. These together with the aging Air Release valve were replaced and Bingo, two hours later, success!

200 PSI 13.8 Bar reading

https://www.nfpa.org/

https://www.lakenheath.af.mil/