Book A Service

News Article

12 - 01 - 2017

Dry Riser testing to NFPA standards

Dry Riser testing to NFPA standards

The testing team were at USAF Lakenheath today carrying out a 200PSI, (13.8 Bar), two hour soak test to the NFPA standards as requested by the client. With the system being around thirty years old, the original valves failed at 6 Bar which was no real surprise. These together with the aging Air Release valve were replaced and Bingo, two hours later, success!

200 PSI 13.8 Bar reading

https://www.nfpa.org/

https://www.lakenheath.af.mil/

News Articles

21 - 04 - 2024

What is the Purpose of a Wet Riser?

When should a wet riser be installed? A wet riser is required in a building 50 meters or higher and is an integral part of...

More

14 - 03 - 2024

Dry Riser Testing & Servicing Frequency

Servicing Requirements for Dry Risers Dry risers sit unused for years but it is vital that they are fully working and accessible when required. For...

More
Dry Risers Direct Limited,

Units 2 & 3 Millbank House,
Riverside Business Park,
Wilmslow,
Cheshire,
England,
SK9 1BJ


Enquire Here

Book Your Service

This website uses Cookies to improve your browsing experience and to help with our marketing. You can read more about removing Cookies here: View Cookies Policy

I'm fine with this